2-Pipe Канален тип с високо статично налягане

220V/1N/50Hz

Capacity range is from 800CFM to 2200CFM.

Description

Introduction

High external static pressure allows extensive ductwork runs and flexible application: ideal for use in shops, medium size offices and large areas.

Specification

Model MKT3H-

800G70
800EG70

1000G70
1000EG70

1200G70
1200EG70

1400G70
1400EG70

Air flow

H/M/L

m3/h

1360/1220/1090

1700/1530/1380

2040/1880/1610

2380/2120/1860

H/M/L

CFM

800/720/640

1000/900/810

1200/1105/950

1400/1250/1095

External Static pressure

Pa

70

70

70

70

Cooling

Capacity

H/M/L

kW

6.6/6.37/6.12

8.8/8.19/7.57

10/9.44/8.53

12/11.47/10.24

Water flow rate

H

l/h

1135

1514

1720

2064

Water pressure drop

H

kPa

8

24

24

36

Heating

Capacity

H/M/L

kW

9.7/8.54/7.18

13.2/11.48/9.9

15/12.9/11.25

17.9/15.75/13.6

Water pressure drop

H

kPa

8.4

25

23.4

34.2

Power supply

V/ph/Hz

220-240/1/50

Power input

H

W

350

350

350

350

Electric heater capacity (‘E)

W

5000

5000

5000

5000

Sound pressure level

H/M/L

dB(A)

49/42/35

50/43/36

51/44/37

52/45/38

Fan motor

Type

Low noise 4-speed fan motor

Quantity

1

Fan

Type

Centrifugal, forward-curved Blades

Quantity

1

1

1

1

Coil

Row

2

3

3

4

Max. Working pressure

MPa

1.6

Diameter

mm

Φ9.52

Body

Dimensions (*/E)

W×H×D

mm

946×400×816 / 946×400×876

Packing (*/E)

W×H×D

mm

1015×480×857 / 1015×480×925

Net weight

*/E

kg

50/53

52/55

52/55

54/57

Gross weight

*/E

kg

55/58

57/60

57/60

59/62

Pipe connection

Water inlet/outlet pipe

Inch

RC3/4

Drain pipe

mm

ODΦ32

Notes:

1.      H: High fan speed; M: Medium fan speed; L: Low fan speed;

2.      Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.

3.      Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.

4.      Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.

Model MKT3H-

1600G100
1600EG100

1800G100
1800EG100

2200G100
2200EG100

Air flow

H/M/L

m3/h

2720/2450/2170

3060/2750/2450

3740/3360/2990

H/M/L

CFM

1600/1440/1280

1800/1620/1440

2200/1980/1760

External Static pressure

Pa

100

100

100

Cooling

Capacity

H/M/L

kW

14.1/13.03/11.87

15.8/14.6/13.46

19.9/18.58/17.24

Water flow rate

H

l/h

2425

2718

3423

Water pressure drop

H

kPa

52

90

130

Heating

Capacity

H/M/L

kW

21.2/18.23/15.69

23.8/20.94/17.85

30/26.7/22.5

Water pressure drop

H

kPa

51

85

121

Power supply

V/ph/Hz

220-240/1/50

Power input

H

W

550

800

950

Electric heater capacity (‘E)

W

9500

9500

9500

Sound pressure level

H/M/L

dB(A)

54/47/40

60/53/46

61/54/47

Fan motor

Type

Low noise 4-speed fan motor

Quantity

1

Fan

Type

Centrifugal, forward-curved Blades

Quantity

2

2

2

Coil

Row

3

3

3

Max. Working pressure

MPa

1.6

Diameter

mm

Φ9.52

Body

Dimensions (*/E)

W×H×D

mm

1290×400×809 / 1290×400×874

Packing (*/E)

W×H×D

mm

1368×460×877 / 1368×460×950

Net weight

*/E

kg

76/82

Gross weight

*/E

kg

83/89

Pipe connection

Water inlet/outlet pipe

Inch

RC3/4

Drain pipe

mm

ODΦ32

Notes:

1.      H: High fan speed; M: Medium fan speed; L: Low fan speed;

2.      Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.

3.      Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.

4.      Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.