Description
Introduction
Stylish unit blends easily with any interior décor; it can easily be mounted in corners and narrow spaces, ideal solution for commercial spaces with narrow or no false ceilings.

|
Model MKF3- |
150 |
250 |
300 |
400 |
450 |
|||
|
Air flow |
H/M/L |
m3/h |
255/215/190 |
425/360/320 |
510/430/380 |
680/580/510 |
765/650/570 |
|
|
H/M/L |
CFM |
150/125/110 |
250/210/190 |
300/250/220 |
400/340/300 |
450/380/335 |
||
|
Cooling |
Capacity |
H/M/L |
kW |
1.15/0.93/0.89 |
1.87/1.74/1.59 |
2.53/2.25/1.88 |
3.27/2.84/2.54 |
3.97/3.58/3.15 |
|
Water flow rate |
H |
l/h |
198 |
322 |
435 |
562 |
683 |
|
|
Water pressure drop |
H |
kPa |
18.3 |
10.1 |
14.2 |
26.3 |
23.1 |
|
|
Heating |
Capacity |
H/M/L |
kW |
2.54/2.24/1.88 |
4.17/3.36/3.13 |
5.64/4.85/4.23 |
7.22/6.35/5.49 |
8.85/7.61/6.55 |
|
Water pressure drop |
H |
kPa |
16 |
8.8 |
13.7 |
24 |
22 |
|
|
Power supply |
V/ph/Hz |
220-240/1/50 |
||||||
|
Power input |
H |
W |
27 |
29 |
40 |
46 |
39 |
|
|
Sound pressure level |
F1 |
H/M/L |
dB(A) |
32/29/26 |
35/32/30 |
37/34/32 |
39/36/34 |
41/38/36 |
|
F2/F3 |
H/M/L |
dB(A) |
30/27/24 |
33/30/28 |
35/32/30 |
37/34/32 |
39/36/34 |
|
|
Fan motor |
Type |
Low noise 3-speed fan motor |
||||||
|
Quantity |
1 |
1 |
1 |
1 |
1 |
|||
|
Fan |
Type |
Centrifugal, forward-curved Blades |
||||||
|
Quantity |
1 |
1 |
2 |
2 |
2 |
|||
|
Coil |
Row |
3 |
3 |
2 |
2 |
3 |
||
|
Max. Working pressure |
MPa |
1.6 |
||||||
|
Diameter |
mm |
Φ9.52 |
||||||
|
Body |
Dimensions |
W×H×D |
mm |
550×545×212 |
550×545×212 |
750×545×212 |
750×545×212 |
950×545×212 |
|
Packing |
W×H×D |
mm |
639×639×305 |
639×639×305 |
839×639×305 |
839×639×305 |
1039×639×305 |
|
|
Net/Gross weight |
kg |
17/19 |
17/19 |
20/23.5 |
20/23.5 |
25/29 |
||
|
Pipe connection |
Water inlet/outlet pipe |
Inch |
G3/4 |
|||||
|
Drain pipe |
mm |
ODΦ16 |
||||||
Notes:
1. H: High fan speed; M: Medium fan speed; L: Low fan speed;
2. Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.
3. Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.
4. Sound level is tested in the semi-anechoic test room.
Specifications are subject to change without prior notice for product improvement.
|
Model MKF3- |
500 |
600 |
800 |
900 |
|||
|
Air flow |
H/M/L |
m3/h |
850/720/640 |
1020/870/765 |
1360/1160/1020 |
1530/1300/1150 |
|
|
H/M/L |
CFM |
500/420/375 |
600/510/450 |
800/680/600 |
900/760/675 |
||
|
Cooling |
Capacity |
H/M/L |
kW |
4.85/4.52/3.72 |
5.64/4.51/3.9 |
6.52/5.75/4.36 |
7.85/7.19/6.55 |
|
Water flow rate |
H |
l/h |
834 |
970 |
1121 |
1350 |
|
|
Water pressure drop |
H |
kPa |
20 |
11.4 |
21 |
24.3 |
|
|
Heating |
Capacity |
H/M/L |
kW |
10.28/9.05/7.71 |
12.24/10.89/9.18 |
15.35/13.82/11.67 |
18.2/16.38/13.65 |
|
Water pressure drop |
H |
kPa |
17.4 |
10 |
20.2 |
21.5 |
|
|
Power supply |
V/ph/Hz |
220-240/1/50 |
|||||
|
Power input |
H |
W |
49 |
63 |
88 |
137 |
|
|
Sound pressure level |
F1 |
H/M/L |
dB(A) |
43/40/38 |
44/41/39 |
46/43/40 |
48/45/42 |
|
F2/F3 |
H/M/L |
dB(A) |
41/38/36 |
42/39/37 |
44/41/38 |
46/43/40 |
|
|
Fan motor |
Type |
Low noise 3-speed fan motor |
|||||
|
Quantity |
1 |
1 |
1 |
1 |
|||
|
Fan |
Type |
Centrifugal, forward-curved Blades |
|||||
|
Quantity |
2 |
3 |
3 |
3 |
|||
|
Coil |
Row |
3 |
2 |
2 |
2 |
||
|
Max. Working pressure |
MPa |
1.6 |
|||||
|
Diameter |
mm |
Φ9.52 |
|||||
|
Body |
Dimensions |
W×H×D |
mm |
950×545×212 |
1250×545×212 |
1250×545×212 |
1250×545×212 |
|
Packing |
W×H×D |
mm |
1039×639×305 |
1339×639×305 |
1339×639×305 |
1339×639×305 |
|
|
Net/Gross weight |
kg |
25/29 |
32/36 |
32/36 |
32/36 |
||
|
Pipe connection |
Water inlet/outlet pipe |
Inch |
G3/4 |
||||
|
Drain pipe |
mm |
ODΦ16 |
|||||
Notes:
1. H: High fan speed; M: Medium fan speed; L: Low fan speed;
2. Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.
3. Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.
4. Sound level is tested in the semi-anechoic test room.
Specifications are subject to change without prior notice for product improvement.
|
Model MKF4(5)- |
150 |
250 |
300 |
400 |
450 |
|||
|
Air flow |
H/M/L |
m3/h |
255/215/190 |
425/360/320 |
510/430/380 |
680/580/510 |
765/650/570 |
|
|
H/M/L |
CFM |
150/125/110 |
250/210/190 |
300/250/220 |
400/340/300 |
450/380/335 |
||
|
Cooling |
Capacity |
H/M/L |
kW |
1.15/0.93/0.89 |
1.87/1.74/1.59 |
2.53/2.25/1.88 |
3.27/2.84/2.54 |
3.97/3.58/3.15 |
|
Water flow rate |
H |
l/h |
198 |
322 |
435 |
562 |
683 |
|
|
Water pressure drop |
H |
kPa |
18.3 |
10.1 |
14.2 |
26.3 |
23.1 |
|
|
Heating |
Capacity |
H/M/L |
kW |
2.54/2.24/1.88 |
4.17/3.36/3.13 |
5.64/4.85/4.23 |
7.22/6.35/5.49 |
8.85/7.61/6.55 |
|
Water pressure drop |
H |
kPa |
16 |
8.8 |
13.7 |
24 |
22 |
|
|
Power supply |
V/ph/Hz |
220-240/1/50 |
||||||
|
Power input |
H |
W |
27 |
29 |
40 |
46 |
39 |
|
|
Sound pressure level |
F4 |
H/M/L |
dB(A) |
32/29/26 |
35/32/30 |
37/34/32 |
39/36/34 |
41/38/36 |
|
F5 |
H/M/L |
dB(A) |
30/27/24 |
33/30/28 |
35/32/30 |
37/34/32 |
39/36/34 |
|
|
Fan motor |
Type |
Low noise 3-speed fan motor |
||||||
|
Quantity |
1 |
1 |
1 |
1 |
1 |
|||
|
Fan |
Type |
Centrifugal, forward-curved Blades |
||||||
|
Quantity |
1 |
1 |
2 |
2 |
2 |
|||
|
Coil |
Row |
3 |
3 |
2 |
2 |
3 |
||
|
Max. Working pressure |
MPa |
1.6 |
||||||
|
Diameter |
mm |
Φ9.52 |
||||||
|
Body |
Dimensions |
W×H×D |
mm |
800×592×225 |
800×592×225 |
1000×592×225 |
1000×592×225 |
1200×592×225 |
|
Packing |
W×H×D |
mm |
889×683×312 |
889×683×312 |
1089×683×312 |
1089×683×312 |
1289×683×312 |
|
|
Net weight |
F4/F5 |
kg |
22.5 |
22.5 |
26 |
26 |
32.5 |
|
|
Gross weight |
F4/F5 |
kg |
26.5 |
26.5 |
31 |
31 |
38 |
|
|
Pipe connection |
Water inlet/outlet pipe |
Inch |
G3/4 |
|||||
|
Drain pipe |
mm |
ODΦ16 |
||||||
Notes:
1. H: High fan speed; M: Medium fan speed; L: Low fan speed;
2. Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.
3. Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.
4. Sound level is tested in the semi-anechoic test room.
Specifications are subject to change without prior notice for product improvement.
|
Model MKF4(5)- |
500 |
600 |
800 |
900 |
|||
|
Air flow |
H/M/L |
m3/h |
850/720/640 |
1020/870/765 |
1360/1160/1020 |
1530/1300/1150 |
|
|
H/M/L |
CFM |
500/420/375 |
600/510/450 |
800/680/600 |
900/760/675 |
||
|
Cooling |
Capacity |
H/M/L |
kW |
4.85/4.52/3.72 |
5.64/4.51/3.9 |
6.52/5.75/4.36 |
7.85/7.19/6.55 |
|
Water flow rate |
H |
l/h |
834 |
970 |
1121 |
1350 |
|
|
Water pressure drop |
H |
kPa |
20 |
11.4 |
21 |
24.3 |
|
|
Heating |
Capacity |
H/M/L |
kW |
10.28/9.05/7.71 |
12.24/10.89/9.18 |
15.35/13.82/11.67 |
18.2/16.38/13.65 |
|
Water pressure drop |
H |
kPa |
17.4 |
10 |
20.2 |
21.5 |
|
|
Power supply |
V/ph/Hz |
220-240/1/50 |
|||||
|
Power input |
H |
W |
49 |
63 |
88 |
137 |
|
|
Sound pressure level |
F4 |
H/M/L |
dB(A) |
43/40/38 |
44/41/39 |
46/43/40 |
48/45/42 |
|
F5 |
H/M/L |
dB(A) |
41/38/36 |
42/39/37 |
44/41/38 |
46/43/40 |
|
|
Fan motor |
Type |
Low noise 3-speed fan motor |
|||||
|
Quantity |
1 |
1 |
1 |
1 |
|||
|
Fan |
Type |
Centrifugal, forward-curved Blades |
|||||
|
Quantity |
2 |
3 |
3 |
3 |
|||
|
Coil |
Row |
3 |
2 |
2 |
2 |
||
|
Max. Working pressure |
MPa |
1.6 |
|||||
|
Diameter |
mm |
Φ9.52 |
|||||
|
Body |
Dimensions |
W×H×D |
mm |
1200×592×225 |
1500×592×225 |
1500×592×225 |
1500×592×225 |
|
Packing |
W×H×D |
mm |
1289×683×312 |
1589×683×312 |
1589×683×312 |
1589×683×312 |
|
|
Net weight |
F4/F5 |
kg |
32.5/35 |
39/36.6 |
39 |
39 |
|
|
Gross weight |
F4/F5 |
kg |
38/40 |
45/42.6 |
45 |
45 |
|
|
Pipe connection |
Water inlet/outlet pipe |
Inch |
G3/4 |
||||
|
Drain pipe |
mm |
ODΦ16 |
|||||
Notes:
1. H: High fan speed; M: Medium fan speed; L: Low fan speed;
2. Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.
3. Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.
4. Sound level is tested in the semi-anechoic test room.
Specifications are subject to change without prior notice for product improvement.
Read more about the product – Here