2-Pipe Канален

220V/1N/50Hz

Capacity range is from 200CFM to 2000CFM.

Description

Introduction

Compact dimensions, can easily be mounted in a ceiling void. Medium external static pressure facilitates unit use with flexible ducts of varying length. It is popular used in hotel bedrooms & small offices.

Specification
Model MKT3-

200G12
200G30
200EG30

300G12
300G30
300EG30

400G12
400G30
400EG30

500G12
500G30
500EG30

600G12
600G30
600EG30

Air flow H/M/L m3/h

340/255/170

510/385/255

680/510/340

850/640/425

1020/765/510

H/M/L CFM

200/150/100

300/225/150

400/300/200

500/375/250

600/450/300

External Static pressure Pa

G12 models: 12; G30 models: 30

Cooling Capacity H/M/L kW

2.2/1.9/1.68

3.1/2.7/2.3

4/3.4/2.95

4.6/3.96/3.45

5.8/4.88/4.45

Water flow rate H l/h

378

533

688

791

998

Water pressure drop H kPa

14

26

18

24

36

Heating Capacity H/M/L kW

3.5/3.08/2.59

5.3/4.61/3.98

6.8/5.85/5.1

7.9/6.95/6

9.8/8.6/7.4

Water pressure drop H kPa

10.5

21.8

16.9

22.3

31.6

Power supply V/ph/Hz

220-240/1/50

Power input 12Pa H W

33

53

66

87

100

30Pa H W

49

64

75

93

114

Electric heater capacity E W

550

650

1100

1100

1600

Sound pressure level 12Pa H/M/L dB(A)

35/32/26

36/33/27

37/34/28

40/36/30

42/38/32

30Pa H/M/L dB(A)

41/37/31

42/38/32

43/39/33

44/40/34

45/41/35

Fan motor Type

Low noise 4-speed fan motor

Quantity

1

1

1

1

1

Fan Type

Centrifugal, forward-curved Blades

Quantity

1

2

2

2

2

Coil Row

3

Max. Working pressure MPa

1.6

Diameter mm

Φ9.52

Body Dimensions W×H×D mm

741×241×522

841×241×522

941×241×522

941×241×522

1161×241×522

Packing W×H×D mm

790×260×550

890×260×550

990×260×550

990×260×550

1210×260×550

Net weight */E kg

14.6/16.1

17/18.5

20.2/21.7

20.2/21.7

23/25

Gross weight */E kg

16.9/18.4

19.5/21

22.6/24.1

22.6/24.1

26/28

Pipe connection Water inlet/outlet pipe Inch

RC3/4

Drain pipe mm

ODΦ24

Notes:

1.      H: High fan speed; M: Medium fan speed; L: Low fan speed;

2.      Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.

3.      Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.

4.      Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.

Model MKT3-

800G12
800G30
800EG30

1000G12
1000G30
1000EG30

1200G12
1200G30
1200EG30

1400G12
1400G30
1400EG30

Air flow

H/M/L

m3/h

1360/1020/680

1700/1275/850

2040/1530/1020

2380/1785/1190

H/M/L

CFM

800/600/400

1000/750/500

1200/900/600

1400/1050/700

External Static pressure

Pa

G12 models: 12; G30 models: 30

Cooling

Capacity

H/M/L

kW

8.2/6.88/6.25

9/7.8/6.57

11/9.8/8.35

12.5/10.8/9.44

Water flow rate

H

l/h

1410

1548

1892

2150

Water pressure drop

H

kPa

39

32

39

45

Heating

Capacity

H/M/L

kW

13.6/11.97/10.2

16/14.24/12

20.1/18.27/15.43

21/18.7/15.75

Water pressure drop

H

kPa

33.8

30.7

34.6

40.1

Power supply

V/ph/Hz

220-240/1/50

Power input

12Pa

H

W

145

180

210

222

30Pa

H

W

154

180

220

278

Electric heater capacity

E

W

2200

2200

3200

3200

Sound pressure level

12Pa

H/M/L

dB(A)

43/39/33

45/41/35

46/42/36

48/44/38

30Pa

H/M/L

dB(A)

46/42/36

47/43/37

48/44/38

49/45/39

Fan motor

Type

Low noise 4-speed fan motor

Quantity

2

2

2

2

Fan

Type

Centrifugal, forward-curved Blades

Quantity

4

4

4

4

Coil

Row

3

Max. Working pressure

MPa

1.6

Diameter

mm

Φ9.52

Body

Dimensions

W×H×D

mm

1461×241×522

1566×241×522

1856×241×522

2022×241×522

Packing

W×H×D

mm

1510×260×550

1615×260×550

1905×260×550

2070×260×550

Net weight

*/E

kg

31.9/34.4

34.4/37.4

39.5/43

43.1/47.1

Gross weight

*/E

kg

35.5/38

38.1/41.1

43/46.5

48.4/52.4

Pipe connection

Water inlet/outlet pipe

Inch

RC3/4

Drain pipe

mm

ODΦ24

Notes:

1.      H: High fan speed; M: Medium fan speed; L: Low fan speed;

2.      Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.

3.      Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.

4.      Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.

Read more about the product – Here