2-Pipe 4-пътен касетъчен тип

220V/1N/50Hz

Capacity range is from 600CFM to 1500CFM.

Description

Introduction

The cassette is designed for use in all forms and sizes of commercial offices & retail environments, enhancing your comfort and providing you better energy efficiency.

Specification
Model MKA-

600R
600RA

750R
750RA

850R
850RA

950R
950RA

1200R
1200RA

1500R

Air flow H/M/L m3/h

1000/850/720

1250/1060/900

1400/1190/1010

1600/1360/1150

2000/1700/1440

2550/2170/1840

H/M/L CFM

590/500/420

740/620/530

820/700/590

940/800/680

1180/1000/850

1500/1280/1080

Cooling Capacity H/M/L kW

5.7/4.73/3.96

7/5.62/4.72

7.27/6.46/5.71

8.22/7.39/6.54

10.39/9.25/8.2

12.9/11.51/10.21

Water flow rate H l/h

980

1204

1250

1414

1787

2219

Water pressure drop H kPa

23.8

25.2

27

31.2

44

40

Heating Capacity H/M/L kW

9.66/7.72/6.27

11.55/9.24/7.51

12.42/9.93/8.07

13.85/11.08/9

17.58/14.06/11.42

17.6/14.08/11.44

Water pressure drop H kPa

16.4

11.8

14.6

14.8

34.7

36.7

Power supply V/ph/Hz

220-240/1/50

Power input H W

125

130

150

155

190

190

Electric heater capacity (A) W

2100

2100

2850

2850

2850

/

Sound pressure level H/M/L dB(A)

45/41/36

46/42/37

47/43/38

48/44/39

49/45/40

50/46/41

Fan motor Type

Low noise 4-speed fan motor

Quantity

1

Fan Type

Centrifugal, forward-curved Blades

Quantity

1

Coil Row

2

2

2

2

2

3

Max. Working pressure MPa

1.6

Diameter mm

Φ7

Panel Dimensions W×H×D mm

950×45×950

Packing W×H×D mm

1035×90×1035

Net weight kg

6

Gross weight kg

9

Body Dimensions W×H×D mm

840×230×840

840×230×840

840×300×840

840×300×840

840×300×840

840×300×840

Packing W×H×D mm

900×260×900

900×260×900

900×330×900

900×330×900

900×330×900

900×330×900

Net weight */A kg

25/27

25/27

30.5/33

30.5/33

30.5/33

31.8

Gross weight */A kg

30/32

30/32

36.2/39

36.2/39

36.2/39

36

Pipe connection Water inlet/outlet pipe Inch

RC3/4

Drain pipe mm

ODΦ32

Notes:

1.      H: High fan speed; M: Medium fan speed; L: Low fan speed;

2.      Cooling conditions: Entering water 7°C, temperature rise 5°C; Entering air temperature 27°C DB/19°C WB.

3.      Heating conditions: Entering water 50°C, the same water flow as the cooling conditions; Entering air temperature 20°C DB.

4.      Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.

Read more about the product – Here