R410A T1 Application 50Hz-ClimaCreator-Series
ClimaCreator-Series-R410A T1 Application 50HzR410A T1 Application-50Hz-Clima-Creator-SeriesR410A-T1 Application 50Hz

R410A T1 Application 50Hz – ClimaCreator Series

R410A T1 Application 50Hz – ClimaMaster Series

Midea rooftop package air conditioners are designed and manufactured to offer the solutions for large halls, warehouses, factories or other applications.

Описание на продукта:

Introduction

R410A refrigerant, Tropical application. The capacity range is from 6.2tons to 30tons. Power supply is 380~415V 3Ph 50Hz

Specification
Model MRC-062HWN1-R(C) MRC-075HWN1-R(C) MRC-085HWN1-R(C) MRC-100HWN1-R(C) MRC-125HWN1-R(C)
Power Supply \ 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz
Cooling Cooling Capacity Btu/h 75000 89000 103000 120000 150000
kW 22 26 30 35 43
Power Input kW 6.6 7.9 9.3 10.7 13.3
Heating Heating Capacity Btu/h 89000 103000 120000 137000 154000
kW 26 30 35 40 45
Power Input kW 7.5 8.9 10.6 11.9 13.2
Max. input consumption kW 8.6 12 13.6 15 19.7
Max. current A 18.3 24.8 26.5 28.8 38.2
Performance Indoor fan air flow CFM 2800 2830 3500 4100 5500
ESP Pa 80 80 80 90 110
EER Btu/h/W 11.4 11.3 11.1 11.2 11.3
COP Btu/h/W 11.8 11.6 11.3 11.5 11.7
Indoor fan Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
Quantity 1 1 1 1 1
Drive type Direct Direct Belt Belt Belt
Compressor Type Scroll Scroll Scroll Scroll Scroll
Quantity 1 1 2 2 2
Outdoor Fan Type Propeller Propeller Propeller Propeller Propeller
Quantity 1 1 1 1 1
Refrigerant Type R410A R410A R410A R410A R410A
Volume kg 5 4.8 2.5+2.5 2.6+2.6 2.1+3.4
Control Piston Piston Piston Piston Piston
Net Weight kg 229 244 340 343 451
Gross Weight kg 234 249 350 354 471
Net dimension (W×H×D) mm 1475×840×1130 1475×840×1130 1483×1138×1231 1483×1138×1231 1965×1230×1130
Packing (W×H×D) mm 1497×867×1152 1497×867×1152 1492×1248×1146 1492×1248×1146 1990×1260×1140

Notes:

1. Cooling capacity test condition:

Outdoor ambient temperature: 35°C, indoor temperature: 26.7°C DB/19.4°C WB.

2. Heating capacity test condition:

Outdoor ambient temperature: 7°C DB/ 6°C WB, indoor temperature: 20°C.

3. Specifications are subject to change without prior notice for product improvement.

Model MRC-150HWN1-R(C) MRC-175HWN1-R(C) MRC-200HWN1-R(C) MRC-250HWN1-R(C) MRC-300HWN1-R(C)
Power Supply \ 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz 380~415V,3Ph,50Hz
Cooling Cooling Capacity Btu/h 180000 208000 240000 300000 360000
kW 53 61 70 87 105
Power Input kW 16.7 19.1 22.6 28.85 35.29
Heating Heating Capacity Btu/h 191000 218000 260000 330000 380000
kW 56 64 75 97 111.5
Power Input kW 17.2 19.5 23.6 30.28 35.19
Max. input consumption kW 25 27 32.5 38.5 42.7
Max. current A 46.1 55.4 63.2 74.3 81.7
Performance Indoor fan air flow CFM 7000 7600 8800 10000 12000
ESP Pa 110 110 120 130 270
EER Btu/h/W 10.8 10.9 10.6 10.4 10.2
COP Btu/h/W 11.1 11.2 11 10.9 10.8
Indoor fan Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
Quantity 1 1 1 1 1
Drive type Belt Belt Belt Belt Belt
Compressor Type Scroll Scroll Scroll Scroll Scroll
Quantity 2 2 2 2 2
Outdoor Fan Type Propeller Propeller Propeller Propeller Propeller
Quantity 1 2 2 2 2
Refrigerant Type R410A R410A R410A R410A R410A
Volume kg 2.85+5.9 5.5+5.5 6.7+6.7 6.0+6.0 7.6+7.6
Control Piston Piston Piston Capillary Capillary
Net Weight kg 492 615 690 940 955
Gross Weight kg 512 645 720 970 985
Net Dimension (W×H×D) mm 1965×1230×1130 2192×1247×1670 2192×1247×1670 2220×1245×2320 2220×1245×2320
Packing (W×H×D) mm 1990×1260×1140 2212×1284×1695 2212×1284×1695 2230×1275×2330 2230×1275×2330

Notes:

1. Cooling capacity test condition:

Outdoor ambient temperature: 35°C, indoor temperature: 26.7°C DB/19.4°C WB.

2. Heating capacity test condition:

Outdoor ambient temperature: 7°C DB/ 6°C WB, indoor temperature: 20°C.

3. Specifications are subject to change without prior notice for product improvement.

Read more about the product – Here

Features

Adjustable Pulley
Through changing the pitch diameter of the pulley mounted on driver shaft, in turn the revolutions per minute of driven shaft will increase or decrease to change air volume.
Adjustable Pulley

Flexible Installation
Flexible Installation

Durable Construction
Pre-painted exterior cabinet panels pass 1000 hours salt-spray test for durability. Weather-resistant construction with capped seams and sloped top panels. G90 galvanized heavy gauge plate conforming to ASTM-A-653, Zinc contenet of galvanized plate is 275g/m2.
Durable Construction

External Pressure Gauge Ports
With gauge ports mounted externally, an accurate diagnostic of system operation can be performed quickly and easily without disrupting airflow.
External Pressure Gauge Ports

Download

File Name Date File Size Click to download
R410A T1 Application 50Hz Technical Manual 20150615 7.02MB download