Description
Introduction
D4 plus series VRF offers a capacity of up to 64HP in 2HP increments by combining up to 4 outdoor units. It is designed to optimize the system and better meet marketneeds.

Model |
D252(8)W |
D280(10)W |
D335(12)W |
D400(14)W |
D450(16)W |
||
Power Supply |
V/Ph/Hz |
380-415/3/50 |
|||||
Capacity |
Cooling* |
RT |
7.2 |
8.0 |
9.5 |
11.4 |
12.8 |
kW |
25.2 |
28 |
33.5 |
40 |
45 |
||
Btu/h |
86,000 |
95,500 |
114,300 |
136,500 |
153,500 |
||
kcal/h |
21,672 |
24,080 |
28,810 |
34,400 |
38,700 |
||
Cooling** |
RT |
7 |
7.4 |
8.7 |
10.5 |
11.7 |
|
kW |
24.5 |
25.8 |
30.8 |
36.7 |
41.24 |
||
Btu/h |
83,940 |
88,030 |
105,090 |
125,220 |
140,580 |
||
kcal/h |
21070 |
22188 |
26488 |
31562 |
35466.4 |
||
Heating |
RT |
7.7 |
8.9 |
10.7 |
12.8 |
14.2 |
|
kW |
27 |
31.5 |
37.5 |
45 |
50 |
||
Btu/h |
92,100 |
107,500 |
128,000 |
153,500 |
170,600 |
||
kcal/h |
23,220 |
27,090 |
32,250 |
38,700 |
43,000 |
||
Power Input |
Cooling* |
kW |
5.79 |
6.83 |
8.17 |
9.64 |
11.25 |
Cooling** |
kW |
7.50 |
8.70 |
10.40 |
12.10 |
14.40 |
|
Heating |
kW |
5.63 |
7 |
8.06 |
9.57 |
11.11 |
|
EER* |
W/W |
4.35 |
4.1 |
4.1 |
4.15 |
4 |
|
EER** |
W/W |
3.27 |
2.97 |
2.96 |
3.03 |
2.86 |
|
COP |
W/W |
4.8 |
4.5 |
4.65 |
4.7 |
4.5 |
|
Max. Input |
kW |
15 |
15 |
17 |
24 |
24 |
|
Max. Current |
A |
28 |
28 |
28 |
42 |
42 |
|
Compressor |
Type×Number |
Digital×1+Fixed×1 |
Digital×1+Fixed×1 |
Digital×1+Fixed×1 |
Digital×1+Fixed×2 |
Digital×1+Fixed×2 |
|
Oil Type |
Digital |
POE |
|||||
Fixed |
POE |
||||||
Oil Charge |
Digital(ml) |
initial: 1893 refill: 1774 |
|||||
Fixed(ml) |
initial: 1656 refill: 1538 |
initial: 1685 refill: 1567 |
|||||
Fan Motor |
Type×Number |
DC×1 |
DC×1 |
DC×1 |
DC×1+AC×1 |
DC×1+AC×1 |
|
Output |
DC(W) |
750 |
750 |
750 |
575 |
575 |
|
AC(W) |
– |
– |
– |
670 |
670 |
||
External Static Pressure |
Pa |
0~20 (default) 20~40 (need to customize) |
|||||
Air Flow |
m3/h |
11,700 |
11,700 |
11,700 |
15,600 |
15,600 |
|
CFM |
6,887 |
6,887 |
6,887 |
9,183 |
9,183 |
||
Sound Pressure Level |
dB(A) |
57 |
57 |
58 |
60 |
61 |
|
Refrigerant |
Type |
R410A |
R410A |
R410A |
R410A |
R410A |
|
Charge |
kg(Ibs) |
9(19.8) |
9(19.8) |
10(22) |
14(30.9) |
14(30.9) |
|
Throttle Type |
EEV(D32MISZ-1R) |
||||||
Design Pressure (Hi/Lo) |
MPa |
4.4/2.6 |
|||||
Pipe |
Liquid Pipe |
mm(inch) |
12.7(1/2) |
12.7(1/2) |
15.9(5/8) |
15.9(5/8) |
15.9(5/8) |
Gas Pipe |
mm(inch) |
25.4(1) |
25.4(1) |
31.8(1 1/4) |
31.8(1 1/4) |
31.8(1 1/4) |
|
Dimension (W×H×D) |
mm |
960×1615×765 |
960×1615×765 |
960×1615×765 |
1250×1615×765 |
1250×1615×765 |
|
inch |
37.8×63.6×30.1 |
37.8×63.6×30.1 |
37.8×63.6×30.1 |
49.2×63.6×30.1 |
49.2×63.6×30.1 |
||
Packing (W×H×D) |
mm |
1025×1790×830 |
1025×1790×830 |
1025×1790×830 |
1305×1790×820 |
1305×1790×820 |
|
inch |
40.4×70.5×32.7 |
40.4×70.5×32.7 |
40.4×70.5×32.7 |
51.4×70.5×32.3 |
51.4×70.5×32.3 |
||
Net Weight |
kg(Ibs) |
240(529) |
240(529) |
240(529) |
335(737) |
335(737) |
|
Gross Weight |
kg(Ibs) |
255(562) |
255(562) |
255(562) |
350(771) |
350(771) |
|
Connectable |
Total Capacity |
% |
50-130 |
||||
Max. Quantity |
13 |
16 |
20 |
23 |
26 |
||
Ambient Temperature Range |
℃ |
Cooling: -15~54 Heating: -15~24 |
Notes: Capacities are based on the following conditions:
Cooling*: Indoor temperature 27℃DB/19℃WB; Outdoor temperature 35℃DB/24℃WB
Cooling**: Indoor temperature 29℃DB/19℃WB; Outdoor temperature 46℃DB/24℃WB
Heating: Indoor temperature 20℃DB/15℃WB; Outdoor temperature 7℃DB/6℃WB
Piping length: Interconnecting piping length 7.5m, level difference of zero.
Conversion Formula: RT=kW×0.284; Kcal/h= kW×860; Btu/h= kW×3412; CFM=m3/h×0.588
The model name D252(8)W is simplified for name MDVT-D252(8)W/RN1-B. It is same as other model name.
Read more about the product – Here