Four-way Cassette Silent Type

220V/1N/50Hz

Capacity range is from 2.8kW to 14kW.

Category:

Description

Introduction

The cassette is designed for use in all forms and sizes of commercial offices & retail environments, enhancing your comfort and providing you better energy efficiency.

Specification

Model

MDV-D28Q4/N1-E

MDV-D36Q4/N1-E

MDV-D45Q4/N1-E

MDV-D56Q4/N1-E

MDV-D71Q4/N1-E

Power supply

220~240-1-50

Cooling

Capacity

kW

2.8

3.6

4.5

5.6

7.1

Power input

W

80

80

88

88

88

Heating

Capacity

kW

3.2

4

5

6.3

8

Power input

W

80

80

88

88

88

Indoor fan motor

Model

YDK26-6S

Type

AC motor

Brand

Weiling, Tongde, Dayang

Insulation class

B

Safe class

IP20

Indoor air flow (H/M/L)

m3/h

764/638//554

764/638//554

905/740//651

905/740//651

950/767//663

Sound pressure level (H/M/L)

dB(A)

32/31/30

32/31/30

36/34/33

36/34/33

38/36/35

Indoor unit body

Net dimension (W×H×D)

mm

840×230×840

Packing size (W×H×D)

mm

955×260×955

Net/Gross weight

kg

21.5/26.7

21.5/26.7

23.7/28.9

23.7/28.9

23.7/28.9

Indoor unit panel

Model

T-MBQ4-02B1

Net dimension (W×H×D)

mm

950×54.5×950

Packing size (W×H×D)

mm

1035×90×1035

Net/Gross weight

kg

42164

Refrigerant type

R410A

Throttle type

EXV

Design pressure (H/L)

MPa

4.4/2.6

Pipe connections

Liquid pipe

mm

Φ6.35

Φ9.53

Gas pipe

mm

Φ12.7

Φ15.9

Drain pipe

mm

Φ32

Controller

Wireless remote controller (RM05/BG(T)E-A)

Notes:

Capacities are based on the following conditions:

Cooling: return air temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent ref. Piping: 8m (horizontal)

Heating: return air temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent ref. Piping: 8m (horizontal)

Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.

Model

MDV-D80Q4/N1-E

MDV-D90Q4/N1-E

MDV-D100Q4/N1-E

MDV-D112Q4/N1-E

MDV-D140Q4/N1-E

Power supply

220~240-1-50

Cooling

Capacity

kW

8

9

10

11.2

14

Power input

W

110

140

165

165

176

Heating

Capacity

kW

9

10

11.1

12.5

16

Power input

W

110

140

165

165

176

Indoor fan motor

Model

YDK37-6S

YDK50-6S

YDK65-6S

YDK65-6S

YDK65-6S

Type

AC motor

Brand

Weiling, Tongde, Dayang

Insulation class

B

Safe class

IP20

Indoor air flow (H/M/L)

m3/h

1200/1021/789

1332/1129/908

1651/1304/1127

1651/1304/1127

1658/1335/1130

Sound pressure level (H/M/L)

dB(A)

42/39/37

43/39/38

45/42/40

45/42/40

46/41/39

Indoor unit body

Net dimension (W×H×D)

mm

840×230×840

840×300×840

Packing size (W×H×D)

mm

955×260×955

955×330×955

Net/Gross weight

kg

23.7/28.9

28.7/34.1

28.7/34.1

28.7/34.1

30.9/36.3

Indoor unit panel

Model

T-MBQ4-02B1

Net dimension (W×H×D)

mm

950×54.5×950

Packing size (W×H×D)

mm

1035×90×1035

Net/Gross weight

kg

42164

Refrigerant type

R410A

Throttle type

EXV

Design pressure (H/L)

MPa

4.4/2.6

Pipe connections

Liquid pipe

mm

Φ9.53

Gas pipe

mm

Φ15.9

Drain pipe

mm

Φ32

Controller

Wireless remote controller (RM05/BG(T)E-A)

Notes:

Capacities are based on the following conditions:

Cooling: return air temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent ref. Piping: 8m (horizontal)

Heating: return air temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent ref. Piping: 8m (horizontal)

Sound level is tested in the semi-anechoic test room.

Specifications are subject to change without prior notice for product improvement.

Read more about the product – Here

Features

Lower operating sound
The new designed fan blade, air deflector and the built-in throttling part make the noise reduced greatly.
More reliableLower operating sound

More reliable
The connection of drainage pan adopts foaming technology which can further improve the connection tightness.
The high voltage and low voltage electricity wires are separated in electronic control box making the interference decreased greatly. Capacitor is isolated by a sheet metal box making it safer and even more reliable.
More reliable

Fresh air intake
Fresh air can enter through the cassette unit so you can enjoy even fresher air in a room.
Fresh air intake

Sub duct
Sub duct enables you to use the same air conditioner unit to cool an additional smaller space nearby.
Sub duct

Easy troubleshooting
By adding digital tube on the display board, Error Codes can be displayed directly for troubleshooting.
Easy troubleshooting

High-lift drain pump
Drain pump can pump condenser water up to 750mm high, which simplifies installation of the drain piping system.High-lift drain pump

Download

File Name Date File Size Click to download
VRF Catalogue 50Hz 2015-6-9 14.12MB download
Four-way Cassette Silent Type TSM 50Hz 2015/7/10 2.25MB download